Execution:
Aggregate type:
stationary
Execution:
Soundproofed
Technical data engine:
Engine manufacturer:
Perkins
Engine:
404A-22G1
Engine No.:
in production
Power:
18.4 KW
Cooling:
Water-cooled
Occasion:
Electric 12 V DC
Speed:
1500 rpm
Fuel:
Fuel oil EN 590
Technical data generator:
Generator manufacturer:
Mecc Alte
Generator type:
NPE32-2M/4C
Gene. No.:
in production
Generator power:
20 kVA
Voltage:
400 / 231 Volt
Power factor:
Cos. - PHI 0.8
Speed:
1500 rpm
Switchgear:
Execution:
Automatic start
Functions:
Hand & Remote Start
Switch:
Generator switch 4 poles
Delivery:
Built
Tank:
Execution:
Base frame tank with drip pan
Content / liter:
90
Dimensions of the power unit:
Width approx. mm:
700
Height approx. mm:
1.650
Length approx. mm:
1.180
Weight approx. KG:
Stock number:
1375
Condition:
New
Year of construction:
2023
Delivery period:
Instant Verl
Hours:
1
Location:
Verl - Germany
Scope of delivery:
Very compact emergency power system with a nominal output of 20 kVA
PRP can be used in confined spaces with only 56 dbA
4 cylinder Perkins industrial diesel engine with 2.22 liter
displacement
Fuel consumption at 50% load 2.90 liters / hour
Fuel consumption at 75% load 4.00 liter / hour
Fuel consumption at 100% load 5.30 liter / hour
Autonomy at 75% load ≈ 23 h
Type Lubricant Oil SAE 15W40
Lubrication capacity l. 10.60
Type Coolant Antifreeze
Coolant capacity l. 12.50
Intake filter paper cassette
Battery Capacity Ah 50
Number of batteries 1
Fuel system and energy balance
AC pump suction lift kPa 1
Combustion air volume flow at LTP capacity (110 %) 87 m³/h
Cooling air flow at LTP capacity (110%) 2,412 m³/h
Exhaust gas flow at LTP Output (110%) 236.4 m³/h
Exhaust gas temperature at LTP power (110 %) 505.00 °C
Max. exhaust gas back pressure kPa 10.20
Exhaust gases heat at LTP power (110 %) 16.60 kWt
Energy on refrigerant at LTP power (110 %) 19.60 kWt
Radiant heat at LTP power (110 %) 4.40 kWt
Control behind a protective flap
With 4-pole miniature circuit breaker
DSE4520 automatic control unit, including:
- Voltmeter, frequency meter, ammeter
- Generator power display (kW, kV Ar, kV A & pf))
-Hour meter
- Tank content in %
- Protection device against overload (kW & kV Ar)
- Protective device against low oil pressure with cut-off
- Protective device against high coolant temperature with shutdown
- Protective device against low fuel level
- Fault on the alternator, battery charger
- Protection device against exceeding the speed (underfrequency)
Emergency stop button
Terminal board for connecting the automatic control panel
Battery charger
Main switch on/off